EasyManua.ls Logo

Allen-Bradley 1794-OF4I - Page 25

Allen-Bradley 1794-OF4I
147 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1794-6.5.8 - January 2010
How to Install Your Analog Module 25
4. If daisy chaining the +24V dc power to the next base unit,
connect a jumper from terminal 51 on this base unit to terminal
34 on the next base unit. Connect the 24V dc common/return
from terminal 33 on this base unit to terminal 16 on the next
base unit.
ATTENTION
Remove field-side power before removing or
inserting the module. This module is designed so
you can remove and insert it under backplane
power. When you remove or insert a module with
field-side power applied, an electrical arc may occur.
An electrical arc can cause personal injury or
property damage by:
sending an erroneous signal to your system’s field
devices causing unintended machine motion
causing an explosion in a hazardous environment
Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating
connector. Worn contacts may create electrical
resistance.
1794-TB3, -TB3T
0
±15
34±51
16±33
A
B
C
Row A
Row B
Row C
Row A
Row B
Row C
1794-TB3S, -TB3TS

Table of Contents