EasyManua.ls Logo

Allen-Bradley 1794-OF4I - Page 60

Allen-Bradley 1794-OF4I
147 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1794-6.5.8 - January 2010
60 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Table 4.5
Analog Input Module (1794-IF4I) Write Configuration Block
Word/Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Word 0 EN000000000000000
Word 1 Chnl 3 Filter Chnl 2 Filter Chnl 1 Filter Chnl 0 Filter
Word 2 Chnl 3 Configuration Chnl 2 Configuration Chnl 1 Configuration Chnl 0 Configuration
Word 3 0 Real Time Sample Programmed Interval
Word 4 IC 1 TR IT 0 0 0 0 RV QK CK GO Channel Number
Where:
EN = Not used on the 1794-IF4I.
IC = Initiate configuration bit
TR = Transparent bit
IT = Interrupt Toggle bit
RV = Revert to defaults bit
QK = Quick calibration
CK = Calibration clock
GO = Gain offset select
Table 4.6
Word/Bit Descriptions for the 1794-IF4I Analog Input ModuleWrite
Write Word Decimal Bit (Octal
Bit)
Definition
Word 0 Bits 00–14 (00–16) Not used. Set to 0.
Bit 15 (17) Output enable bit (EN). – Not used in the 1794-IF4I module.
Word 1 Channels 0 through 3 Filter Selections (refer to Table 4.7 )
Bits 00–03 Channel 0 Filter Setting
Bits 04–07 Channel 1 Filter Setting
Bits 08–11 (10–13) Channel 2 Filter Setting
Bits 12–15 (14–17) Channel 3 Filter Setting
Word 2 Channel Configuration (refer to Table 4.B )
Bits 00–03 Channel 0 Configuration
Bits 04–07 Channel 1 Configuration
Bits 08–11 (10–13) Channel 2 Configuration
Bits 12–15 (14–17) Channel 3 Configuration
Word 3 Bits 00–14 (00–16) Real Time Sample Interval – Programs the interval of the real time sample. Can be varied
from 0 to 30 seconds (30000 decimal). Resolution is in ms with granularity in 5ms steps.
Bit 15 (17) Not used. Set to 0.