FLEX I/O Isolated Output HART Analog Module 17
Publication 1794-IN120D-EN-P - September 2015
Format Values
Cyclic HART Input Data
The HART input data holds the primary variables for the “live” HART device, and other
information gathered during the normal HART scan. Additional “documentary” data is
available through the pass through message interface in the device information tables. Pass
through messages are defined in detail in the User Manual.
HART Input Data
Format Format Name 0.0 mA 2.0 mA 4.0 mA 20.0 mA 22.0 mA
0 0...20 mA in Milliamps 0 2000 4000 20000 22000
1 0...20 mA in % Full Scale 0 1000 2000 10000 11000
3 0...20 mA in UINT 0 6554 13107 65535 65535
(1)
4 4...20 mA in Milliamps 2000
(1)
(1)
These values are under, or over the supported user range, and are clamped at the lowest/highest supported values.
2000 4000 20000 22000
7 4...20 mA in UINT 0
(1)
0
(1)
0 65535 65535
(1)
14 4...20 mA in % Full Scale -1250
(1)
-1250 0 10000 11250
The HART Input Data for a channel may be zeroes if HART communications
is disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
CMD 3 Disable functions in the Configuration Map table.
Word Bit
1514131211109876543210
0 Reserved CH7 CH6 CH5 CH4 CH3 CH2 CH1 CH0
(HART CMD 3 Communication Status)
1 Reserved
2 CH0 HART Field Device Status CH0 HART Comm Status
3 Reserved FVA TVA SVA PVA CH0 HART Loop Status
4 CH0 HART Primary Value (IEEE 754-1985 Single-Precision 32-bit floating point)
5