EasyManua.ls Logo

Allen-Bradley 2080-LC20-20QBB

Allen-Bradley 2080-LC20-20QBB
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2080-UM005E-EN-E - March 2018 61
Communication Connections Chapter 5
CIP Symbolic Addressing
Users may access any global variable through CIP Symbolic addressing except for
system and reserved variables.
One- or two-dimension arrays for simple data types are supported (for example,
ARRAY OF INT[1..10, 1..10]) are supported but arrays of arrays (for example,
ARRAY OF ARRAY) are not supported. Array of strings are also supported.
CIP Client Messaging
CIP Generic and CIP Symbolic messages are supported on Micro800 controllers
through the Ethernet and serial ports. These client messaging features are enabled
by the MSG_CIPSYMBOLIC and MSG_CIPGENERIC function blocks.
See Micro800 Programmable Controllers: Getting Started with CIP Client
Messaging, publication 2080-QS002
, for more information and sample
quickstart projects to help you use the CIP Client Messaging feature.
Supported Data Types in CIP Symbolic
Data Type
(1)
(1)
Logix MSG instruction can read/write SINT, INT, DINT, LINT and REAL data types using “CIP Data Table Read”
and “CIP Data Table Write” message types.
BOOL, USINT, UINT, UDINT, ULINT, LREAL, STRING, SHORT_STRING, DATE, and TIME data types are not
accessible with the Logix MSG instruction.
Description
BOOL Logical Boolean with values TRUE(1) and FALSE(0)
(Uses up 8 bits of memory)
SINT Signed 8-bit integer value
INT Signed 16-bit integer value
DINT Signed 32-bit integer value
LINT
(2)
(2)
Not supported in PanelView Component or PanelView 800.
Signed 64-bit integer value
USINT Unsigned 8-bit integer value
UINT Unsigned 16-bit integer value
UDINT Unsigned 32-bit integer value
ULINT
(2)
Unsigned 64-bit integer value
REAL 32-bit floating point value
LREAL
(2)
64-bit floating point value
STRING Character string (1 byte per character)
DATE
(3)
(3)
Can be used by sending data to UDINT, mainly for use with PanelView Plus and PanelView 800 HMI terminals.
Unsigned 32-bit integer value
TIME
(3)
Unsigned 32-bit integer value

Table of Contents

Related product manuals