10 Rockwell Automation Publication 193-UM013B-EN-P - December 2019
Chapter 2 System Operation and Configuration
Set the Trip Current
When you set the trip current, you must consider the motor service factor and
FLA. You can find this information on the motor nameplate, as shown in Ta b le 1
and Tab le 2
.
Table 1 - Service Factor/Motor FLA Dial Settings
Table 2 - Service Factor/Motor FLA Dial Settings
Service Factor Trip Current Setting
<1.15 0.9 x FLA
≥ 1.15 1 x FLA
YΔ (Star-Delta) FLA/1.73
Service Factor Trip Current Setting
YΔ (Star-Delta) FLA/1.73
Direct-on-line 1 x FLA