10 Rockwell Automation Publication 520-TD002A-EN-E - May 2015
PowerFlex 527 AC Drive Specifications
Control Outputs
Encoder
Safety
(per
channel)
Input Current: <10 mA
Input ON Voltage, max: 18...26.4V DC
Input OFF Voltage, max: 5V DC
Input ON Current: 10 mA
Input OFF Current: 500 µA
Pulse Rejection Width: 700 µs
External Power Supply: SELV/PELV
Input Type: Optically isolated and reverse voltage protected
Specifications PowerFlex 527
Relay Quantity: (2) 1 Programmable Form A and 1 Programmable Form B
Specification
Resistive Rating:
Inductive Rating:
3.0 A @ 30V DC, 3.0 A @ 125V, 3.0 A @ 240V AC
0.5 A @ 30V DC, 0.5 A @ 125V, 0.5 A @ 240V AC
Opto Quantity: (2) Programmable
Specification: 30V DC, 50 mA Non-inductive
Analog Quantity: (1) Non-Isolated 0-10V or 4-20 mA
Specification
Resolution:
0-10V DC Analog:
4-20 mA Analog:
10-bit
1 k ohm minimum
525 ohm maximum
Specifications PowerFlex 527
Type: Incremental, dual channel
Supply: 5V, 12V, 250 mA
Quadrature: 90°, ±27° @ 25 °C
Duty Cycle: 50%, +10%
Requirements: Encoders must be line driver type, quadrature (dual channel), 3.5...26V DC output, single-ended or differential and capable of supplying
a minimum of 10 mA per channel.
Allowable input is DC up to a maximum frequency of 250 kHz. The encoder I/O automatically scales to allow 5V, 12V and 24V DC nominal
voltages.
Specifications PowerFlex 527