Publication 20A-IN009C-EN-P
26 PowerFlex® 70 Adjustable Frequency AC Drive Installation Instructions
E B
D
E
JP1/JP2
Installed
JP3/JP4
Not Installed
Solid Ground
Jumpers should be installed at both
locations (JP1/JP2 and JP3/JP4).
Non-Solid Ground
Remove the jumper at “JP1/JP2.” Verify
that the jumper at “JP3/JP4” is also
removed.
CJP1/JP2
Installed
JP3/JP4
Installed
Frame
Voltage
Code
Factory Default Jumper Settings
Power Source TypeMOV/Input Filter Caps
DC Bus Common
Mode Caps
JP1 JP2
JP4
JP3
MOV /
Filter Cap
CM Cap