Category Specification Frames 1…6 (690V Drive - Frames 5 & 6 Only) Frames 9 & Up
Environment Altitude: 1,000 m (3,300 ft.) max. without derating (See Altitude Derating on page 107)
Surrounding Air Temperature
without Derating:
Based on the drive rating. See tables in Drive Power Ratings on
page 51.
Note: Frames 9 & 10 are rated 0° to 40° C (32° to 104° F) air
temperature surrounding the drive module.
Open Type:
0° to 50° C (32° to 122° F)
IP20:
0° to 50° C (32° to 122° F)
NEMA/UL Type 1:
0° to 40° C (32° to 104° F)
IP56, NEMA/UL Type 4X:
0° to 40° C (32° to 104° F)
Storage Temperature (all const.): –40° to 70° C (-40° to 158° F) –40° to 70° C (–40° to 158° F)
Relative Humidity: 5% to 95% non-condensing 5% to 95% non-condensing
Shock: 10G peak for 11 ms duration (1.0 ms) 15G peak for 11 ms duration (1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz 2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Sound: Frame Fan Speed Sound
Level
Note: Sound pressure level is
measured at 2 meters.
Frame Sound
Level
Back-ground
Noise Level
Note: Sound pressure level
is measured at 1 meter. All
devices that are measured
are 400V IP21 and in
power-up mode.
1 30 CFM 59 dB 9 78 49
2 50 CFM 57 dB 10 77 49
3 120 CFM 61 dB 13 76 46
4 190 CFM 59 dB
5 200 CFM 71 dB
6 300 CFM 72 dB
Atmosphere: Important: Drive
must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors, or dust. If the drive
is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Electrical AC Input
(Six-Pulse, Three-Phase)
Voltage Tolerance:
(See Voltage Tolerance on page 107 for Full Power and Operating Range) (See Voltage Tolerance on page 107 for Full Power and Operating
Range)
Frequency Tolerance:
47…63 Hz 47…63 Hz.
Input Phases:
Six-pulse, three-phase input provides full rating for all drives. Single-
phase operation provides 50% of rated current.
Six-pulse, three-phase input provides full rating for all drives. Single-
phase operation provides 20% of rated current.
DC Input
Voltage Tolerance:
10% of Nominal Bus Voltage (above) 10% of Nominal Bus Voltage (above)
Displacement Power Factor: 0.98 across speed range 0.98 across speed range
Efficiency: 97.5% at rated amps, nominal line volts 97.5% at rated amps, nominal line volts
Max. Short Circuit Current Rating:
Using Recommended Fuse or
Circuit Breaker Type:
Maximum short circuit current rating to match specified fuse/circuit
breaker capability.
200,000 Amps 200,000 Amps
Maximum Drive to Motor Power
Ratio:
The drive to motor rating cannot exceed a 2:1 ratio The drive to motor rating cannot exceed a 2:1 ratio