Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 37
PowerFlex 700S Drives with Phase II Control
690V Shielded/Unshielded Cable - Meters (Feet)
Drive No Solution Reactor Only Reactor + Damping Resistor Reactor Resistor Available Options
Frame kW kHz 1850V 2000V 1850V 2000V 1850V 2000V Cat. No. Ohms Watts
TFA1
TFB2
RWR2
RWC
5 45 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 345/690
55 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R80-C 50 345/690
75 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R100-C 50 345/690
90 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R130-C 50 375/750
6 110 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R160-C 50 375/750
132 2/4 30.5 (100) 76.2 (250) 91.4 (300) 152.4 (500) 365.8 (1200) 365.8 (1200) 1321-3R200-C 50 375/750
9 160 2 30.5 (100) 68.6 (225) 91.4 (300) 152.4 (500) 274.3 (900) 365.8 (1200) 1321-3RB250-C 50 480
200 2 30.5 (100) 68.6 (225) 91.4 (300) 152.4 (500) 274.3 (900) 365.8 (1200) 1321-3RB250-C 50 480
10 250 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 274.3 (900) 365.8 (1200) 1321-3RB320-C 50 480
315 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 274.3 (900) 365.8 (1200) 1321-3RB400-C 20 945
(3)
(3) Resistor specification is based on two cables per phase.
355 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 274.3 (900) 365.8 (1200) 1321-3R500-C 20 945
(3)
400 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 243.8 (800) 304.8 (1000) 1321-3R500-C 20 945
(3)
11 450 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 243.8 (800) 304.8 (1000) 1321-3R600-C 20 945
(3)
500 2 30.5 (100) 68.6 (225) 76.2 (250) 121.9 (400) 243.8 (800) 304.8 (1000) 1321-3R600-C 20 945
(3)
560 2 30.5 (100) 68.6 (225) 61.0 (200) 91.4 (300) 243.8 (800) 304.8 (1000) 1321-3R750-C 20 945
(3)
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
630 2 30.5 (100) 68.6 (225) 61.0 (200) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3RB400-C 40 480
(3)
710 2 30.5 (100) 68.6 (225) 61.0 (200) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3R500-C 40 645
(4)
(4) Resistor specification is based on three cables per phase.
800 2 30.5 (100) 68.6 (225) 61.0 (200) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3R500-C 40 645
(4)
13 900
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2 30.5 (100) 68.6 (225) 61.0 (200) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3R600-C 40 645
(4)
1000
(2)
2 30.5 (100) 68.6 (225) 48.8 (160) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3R600-C 20 840
(5)
(5) Resistor specification is based on four cables per phase.
1100
(2)
2 30.5 (100) 68.6 (225) 48.8 (160) 91.4 (300) 243.8 (800) 304.8 (1000) 2 X 1321-3R750-C 20 840
(5)