56 Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Set the Start, Stop, and Speed Reference Commands via the EtherNet/IP Adapter
By default, the Start and Stop commands are enabled over the EtherNet/IP adapter. To set the speed reference via the
EtherNet/IP adapter, set parameter 545 [Spd Ref A Sel]. See Ta b le
37.
Table 36 - PowerFlex 755 Embedded EtherNet/IP Port 13 Parameter Settings
No. Drive
Parameter
Name
User
Setting
Default Value/Options Notes
33 Port Number 13 0
36 BOOTP 0 1 0 = Disabled
1 = Enabled
A reset of the adapter is required. Reset the adapter by power cycling the drive or by using
the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
38 IP Addr Cfg 1 192 Example IP Address.
39 IP Addr Cfg 2 168 0
40 IP Addr Cfg 3 1
41 IP Addr Cfg 4 xxx Set to desired value.
42 Subnet Cfg 1 255
43 Subnet Cfg 2 255
44 Subnet Cfg 3 255
42 Subnet Cfg 4 0
Leave the remainder of the Embedded EtherNet/IP (P
ort 13) parameters at their default settings.
Table 37 - Speed Reference Parameter Setting
No. Drive
Parameter
Name
User
Setting
Default Value/Options Notes
545 Spd Ref A Sel 877 871 P871 = Port 1 HIM reference
P877 = Port 13 reference
Selects the source parameter number for the speed reference while in “Auto” (typical)
mode. Reference value from port devices. For a speed reference from a communication
network, set this parameter to Port 0 and select P871…877 [Port_n_Reference] as
appropriate.
Important Example: 20-
COMM-E, EtherNet/IP Communication Adapter = Dint for speed
reference multiplied by 1,000 (60 Hz = 60,000 and 1750 RPM = 1,750,000).