Electrical Requirements
94
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT Part No. 70458301ENR7
230-240V/50Hz/3ph L1, L2, L3, and
ground
62 N/A 80A* – 3 pole 4 (25)
240V/60Hz/3ph L1, L2, L3, and
ground
62 62 80A* – 3 pole 4 (25)
380V/50 or
60Hz/3ph
L1, L2, L3, and
ground
38 38 50A* – 3 pole 6 (16)
400-415V/50Hz/3ph L1, L2, L3, and
ground
35 35 45A* – 3 pole 8 (10)
440V/60Hz/3ph L1, L2, L3, and
ground
33 N/A 45A* – 3 pole 8 (10)
460-480V/60Hz/3ph L1, L2, L3, and
ground
31 31 40A* – 3 pole 8 (10)
* 3 Phase machines should not have fuses, breakers only.
N/A = Not Applicable
Table 23
12 kW Eco Line 035 Series Electric Models
Serial Plate Amps Recommended CircuitSerial Plate
Voltage
Terminal Block
Connections
Required
Nonreversing Reversing Breaker Rating Wire Size AWG
(mm
2
)
380V/50Hz/3ph L1, L2, L3, and
ground
19.3 19.3 25A* – 3 pole 10 (6)
400-415V/50Hz/3ph L1, L2, L3, and
ground
17.8 17.8 25A* – 3 pole 10 (6)
* 3 Phase machines should not have fuses, breakers only.
Table 24
27 kW Classic Line 055 Series Electric Models
Serial Plate
Voltage
Terminal Block
Connections
Required
Serial Plate Amps Recommended Circuit