EasyManua.ls Logo

Alliance Laundry Systems UTF75N - Airflow Optimization (Cyclonic Lint and Airflow Management System Models Only)

Alliance Laundry Systems UTF75N
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Airflow Optimization (Cyclonic Lint and
Airflow Management System models
only)
The control will regulate the fan speed based on information re-
ceived from the input/output board. The spin speed will increase
or decrease, within a defined range between the maximum and
minimum spin speeds, depending how the current temperature
reading compares to the previous temperature reading. This fea-
ture is only available if the second thermistor is installed and the
control is configured for it and only happens in Run Mode for
heat cycles during the drying phase. If the thermistor reaches its
high limit, the heat will turn off and remain off until the thermis-
tor reaches its low limit. If the control is not able to read a tem-
perature from the input/output board, the control will not use Air-
flow Optimization and will set the fan to its nominal spin speed.
Special Features
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
16 Part No. 70705301ENR2

Table of Contents

Other manuals for Alliance Laundry Systems UTF75N

Related product manuals