508433-01Issue 2345Page 56 of 70
Maintenance
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
At the beginning of each heating season, system should
be checked as follows by a qualied service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
The blower access panel must be securely in place
when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
WARNING
Filters
All air lters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the lters when
necessary to ensure proper furnace operation. Table 21
lists recommended lter sizes.
If a high-eciency lter is being installed as part of this
system to ensure better indoor air quality, the lter must
be properly sized. High-eciency lters have a higher
static pressure drop than standard-eciency glass/foam
lters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop
may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any lter with this system, check the
specications provided by the lter manufacturer
IMPORTANT
Cabinet Width
Filter Size
Side Return Bottom Return
17-1/2”
16 x 25 x 1 (1)
16 x 25 x 1 (1)
21” 20 x 25 x 1 (1)
24-1/2” 16 x 25 x 1 (2) 24 x 25 x 1 (1)
Table 21.
Exhaust and Air Intake Pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE: After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
Fire Hazard. Use of aluminum wire with this product
may result in a re, causing property damage, severe
injury or death. Use copper wire only with this product.
WARNING
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specications and unit rating
plate.
CAUTION
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC + 10%
3. Check amp-draw using a true RMS meter on the
blower motor with blower access panel in place. See
Figure 56.
Unit Nameplate_____________ Actual____________
Figure 56. Check Motor Amp Draw
kVAr
kWh
COMM
V3
V1
V2
P
OFF
MR
EX
1
W
3
2
True RMS Meter