PF: Protection of Parameters
Function
code
Function
Name
LCD
Display
Range of settings
Default
Change
MODB
US
Address
PF.00
User
password
User
password
0: No password
Others: Password
protection
0
1000
PF.01
Parameter
write-in
protection
Paramete
r
selection
protectio
n
0: All parameters are
allowed to modify
1: Only reference
frequency (P0.00)
and PF.01 can be
modified;
2: Only PF.01 can be
modified.
0
1001
PF.02
Parameter
initializati
on
Paramete
r
initializat
ion
0: No operation
1: Clear fault history
2: Restore default
(except recorded data
\ user password)
0
× 1002
Reserve
(3004GB
or below)
Reserved Reserved 0
-
PF.03
Parameter
copy
(35R5GB/
37R5PB or
above)
Paramete
r copy
0: No action
1: Parameters
download
2: Parameters upload
3: Download
parameters except
motors
Note: This function is
only valid for LCD
keyboard.
0
×
1003
PF.04
G/P
selection
G/P
selection
0: Type G (
Constant
torque)
1: Type P (Inlet fan
and pump series
loads)
0
× 1004