Chapter6 Troubleshooting
http://www.acdrive-china.com
191
Fault
display
Name of
protection
Possible reasons of fault Actions
OC2
Over current
in Dec process
Too short decelerating
time
Inertia torque of the
load is big.
Too low ac drive’s
power
Output load of the ac
drive is short circuited
Increase decelerate time
Add appropriate braking
component
Select a high-power ac
drive
Check resistance of the
motor’s winding; check
insulation of the motor
OC3
Over current
in
constant-speed
Operation
Abnormity Load
Too short accelerating/
decelerating time setting
Low voltage of power
supply
Too low ac drive’s
power
Output load of the ac
drive is short circuited
Check the load
Add accelerate/decelerate
time properly
Check input power supply
Select the ac drive with
higher power
Check resistance of the
motor’s winding; check
insulation of the motor
Ou1
Over Voltage
in acceleration
process
Abnormity Input
voltage
Too short accelerating
time setting
Check input power
supply/ the setting of
detection level
Increase accelerating
time.
Ou2
Over voltage
in
deceleration
process
Abnormity input
voltage
Too short decelerating
time setting
Inertia torque of the
load is big
Check input power
supply/ the setting of
detection level
Increase decelerating time
properly
Add appropriate braking
component
Ou3
Over voltage
in constant
speed
Operation
Abnormity input
voltage
Too short accelerating/
decelerating time setting
Inertia torque of the
load is big
Check input power
supply/ the setting of
detection level
Increase decelerating time
properly
Add appropriate braking
component