Alpha E-Tec Plus 28NX, 33NX and 38NX - Commissioning
ID
Parameter Description Range
0 - 100
0 - P2
0 - 100
0 - 1
0 - 12
0 - 12
0 - 12
0 - 12
0 - 3
-9 - 9K
DHW max.
CH min.
CH max.
Pump functioning
On board relays
(5 - 6)
Relay 1 on relay
board (optional)
Relay 2 on relay
board (optional)
Relay 3 on relay
board (optional)
Standby/off
configuration
External probe
reading correction
P. 0
P. 1
P. 2
P. 3
P. 4
P. 5
P. 6
P. 7
P. 8
P. 9
Default
100
0
E-Tec Plus
28NX
NG = 83
LPG = 83
E-Tec Plus
33NX
NG = 86
LPG = 86
E-Tec Plus
38NX
NG = 84
LPG = 84
0
0
0
0
0
0
0
Customised
value
Defines the max. heat output percentage of the boiler during
DHW phase compared to the max. heat output available
Defines the min. output percentage of the boiler in CH mode
Defines the max. output percentage of the boiler in CH mode
The pump can be operated in two modes:
0 - Intermittent - In winter 'mode' the pump is controlled by the
room thermostat or remote control
1 - Continuous - In winter 'mode' the pump is always
energised, therefore always running
Setting a value other than zero is not acceptable if the function
is already present in another relay:
0 - OFF
1 - Zone 1 control (with Climatic)
2 - Zone 2 control
3 - General alarm
4 - Alpha trace heating kit enabled
5 - Flow Smart
6 - External pump
7 - Not used
8 - External system 3-way valve
9 - Boiler pump active
10 - Chiller remote activation
11 - Not used
12 - Not used
Setting a value other than zero is not acceptable if the function
is already present in another relay:
0 - OFF
1 - Zone 1 control (with Climatic)
2 - Zone 2 control
3 - General alarm
4 - Alpha trace heating kit enabled
5 - Flow Smart
6 - External pump
7 - External gas valve
8 - External system 3-way valve
9 - Boiler pump active
10 - Chiller remote activation
11 - Not used
12 - Not used
See notes P.5
See notes P.5
0 - Antifreeze, anti-block
1 - Antifreeze off, anti-block
2 - Antifreeze and anti-block off
3 - Not used
If the reading of the external probe is not correct it is possible
to correct it in order to compensate any environmental factors
41