103448-07 - 1/16 9
Table 2: Ratings
I. Product Description, Specications and Dimensional Data (continued)
Alpine Series Gas-Fired Boilers
Model Number
Input (MBH)
Heating Capacity
(MBH)
Net AHRI Ratings Water
1
(MBH)
AFUE
(%)
Min. Max.
ALP080B 16 80 72 63 95
ALP105B 21 105 96 83 95
ALP150B 30 150 136 118 95
ALP210B 42 210 194 169 95
ALP285B 57 285 262 228 95
Ratings shown are for installations at sea level and elevations up to 2000 ft. For elevations above 2000 ft., the boiler will
naturally derate by 2.5% for each 1000 ft. above sea level - applicable to ALP080B thru ALP210B.
ALP285B rating is for installation at sea level and elevations up to 7800 ft. For elevations above 7800 ft., the boiler will
naturally derate by 1.8% for each 1000 ft. above sea level.
1
Net AHRI Water Ratings based on allowance of 1.15. Consult manufacturer before selecting boiler for installations
having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
II. Unpacking Boiler
CAUTION
Do not drop boiler.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container.
D. Remove boiler from cardboard positioning sleeve on
shipping skid.
WARNING
Installation of this boiler should be undertaken
only by trained and skilled personnel from a
qualied service agency.
E. Move boiler to its permanent location.