INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
ALPINE
CONDENSING HIGH EFFICIENCY
DIRECT VENT
GAS - FIRED HOT WATER BOILER
Size Range - 80 MBH through 285 MBH

Table of Contents

Questions and Answers

  • D
    Denise CampbellSep 23, 2025
    Why has the supply temperature risen too quickly on my Alpine ALP150B Boiler?
    • J
      Joyce RuizSep 23, 2025
      Inadequate boiler water flow.
  • S
    Suzanne ClarkAug 23, 2025
    What to do if my Alpine ALP150B Boiler is not responding to heat call?
    • J
      Joseph MasonAug 23, 2025
      If your Alpine Boiler isn't responding to a call for heat and the status and priority show standby, the boiler isn't detecting the call for heat. Check the thermostat or zone wiring for loose connections, miswiring, or a defective thermostat/zone control.
  • L
    Linda SalazarAug 25, 2025
    Why is the green power light blinking on my Alpine ALP150B Boiler control?
    • M
      mariaharperAug 26, 2025
      A blinking green power light on the control indicates a control fault. The internal power supply is repeatedly starting and stopping. Try disconnecting all terminals except 24VAC to power the Control. The green light should be steady. If it is not, then the control is defective. If steady, start plugging in all the connectors while watching the green light. When faulty wiring reconnected, green light will begin to flash.
  • J
    Johnathan WhiteAug 27, 2025
    What causes a Boiler Safety Limit Open (Condition 2) on an Alpine ALP150B Boiler?
    • M
      Matthew RiveraAug 27, 2025
      A Boiler Safety Limit Open (Condition 2) indicates that the boiler safety limit wired to terminals J6-1, 2, or 3 is open. Potential causes include loose wiring to the limit device, an auto-reset supply high limit sensor detecting a temperature in excess of 200°F.
  • J
    Joseph SandersAug 27, 2025
    Why is my Alpine Boiler display dark but the fan is running?
    • E
      Eduardo CraigAug 27, 2025
      If the display is completely dark, but the fan is running, the issue is likely a lack of 24Vac power to the control. Check for loose 120Vac connection wiring between the boiler J-Box and the transformer, or loose 24 Vac connection wiring between the transformer and the control.
  • S
    Sheryl GibsonSep 16, 2025
    Why is my Alpine ALP150B Boiler display dark but the boiler still fires?
    • M
      Michael WardSep 16, 2025
      If the display is completely dark but the boiler fires, the issue is likely a lack of 5 Vdc power to the display. Check for a loose 5 Vdc connection wiring between the display and the control, or a defective display or control.
  • L
    Lisa WhiteSep 13, 2025
    What causes ignition failure on Alpine ALP150B Boiler?
    • P
      Paul ReeseSep 13, 2025
      Ignition failure (Condition 11) on models ALP080B through ALP285B means flame failure after 5 tries to restart. Possible causes include no gas pressure.
  • S
    Shari DeanSep 14, 2025
    What does DT inlet/outlet high mean on my Alpine Boiler?
    • C
      charleshughesSep 15, 2025
      A high DT inlet/outlet indicates that the temperature rise between the supply and return is too high. This can be due to inadequate boiler water flow. Verify that the circulator is operating and that the circulator and piping are sized per Section VI of this manual.
  • N
    Nicole GonzalezSep 5, 2025
    What does a stack sensor fault mean on Alpine ALP150B Boiler?
    • H
      Heather PeckSep 5, 2025
      A stack sensor fault indicates a shorted or open flue gas (stack) temperature sensor. Check for shorted or mis-wired flue temperature sensor wiring, or a defective flue temperature sensor.
  • K
    Kristie MckeeSep 3, 2025
    What causes a return sensor fault on an Alpine ALP150B?
    • T
      Thomas JonesSep 3, 2025
      A return sensor fault indicates a shorted or open return temperature sensor. This can be due to shorted or mis-wired return sensor wiring, or a defective return sensor.