Installation
Calculating the SF
6 gas filling pressure
For u sing th e pressure gau g e (tools)
P31--9001EN/02
3/4
01--2011
© ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, without express written authority, is
strictly prohibited.
GRID
Calculating the filling pressure on site
Measuring
Write the measurements in the corresponding boxes :
Measure the atmospheric pressure in MPa.
A ,
Measure the ambient temperature in °C.
B
Calculating the SF
6
gas filling pressure
Read the values inthe corresponding boxes and write down the results:
Using the table (page 4) ”Relative pressure values for SF
6
gas corrected for temperature,” determine the value ”p
re
”
corrected according to the
ambient temperature (B) "
p
re
C ,
Reference atmospheric pressure value in MPa
D0, 101
Read the local atmospheric pressure value
(A) "
A
--
,
Calculate the atmospheric pressure variation
(D--A) "
E ,
Read the value (C) "
C
+
,
Calculate the assigned relative pressure
(E+C) "
F ,
Filling with SF
6
gas will take place until the
calculated pressure,increased by 0,01 MPa.
+ 0 , 01
(F + 0.01) "
G ,