Choose proper shielding cable and strip jacket, braiding wire, and insulation to specified dimensions.
Load copper ferrule onto braiding wire to the bottom, ensuring no loose shielding strands are uncovered.
Crimp copper ferrule with hexagonal tool, ensuring minimum retention strength of 50N.
Crimp terminal onto wire, meeting minimum tensile strength requirements (222.5N for 2.5mm²/14AWG, 311.5N for 4mm²/12AWG).
Insert cable with crimped terminal into the connector, repeating for the second cable.
Select proper shielding cable and strip jacket, braiding wire, and insulation to specified dimensions.
Crimp terminal onto wire, meeting minimum tensile strength requirements (356N for 6mm²/10AWG, 400.5N for 10mm²/8AWG).
Load shielding gasket, seal, and cover onto the cable sequentially.
Load metal gasket, ensuring braiding wire is between the shielding gasket and metal gasket.
Push terminal components into the shell, ensuring keyway on cover matches the key on the shell.
| Series | PowerLok 4.0 |
|---|---|
| Contact Material | Copper Alloy |
| Plating | Silver |
| Housing Material | Thermoplastic |
| Operating Temperature | -40°C to +125°C |
| Application | Power Distribution |
| Product Category | Connectors |
| Ingress Protection | IP67 |
| Standards | UL 1977 |
| Number of Positions | 1 |
| Contact Gender | Male |