Amtech
6-20
6
No.
Parameter
Unit
Def
Min
Max
Res
Description
WP
C323
Static Pot Option
during stop
1 1 5 1 This parameter provides selection of the static
pot speed at stop.
=1: Last Speed
=2: Min Frequency
=3: Max Frequency
=4: A101 Set Freq
=5: B401 Preset Speed-1
C324
Panel
Temperature Limit
60 25 70 1 This parameter is set limit for panel temperature
fault when IU/DU system is in use.
GROUP
-
4: SERIAL COMMUNICATION
C401
Baud Rate bps 4 1 6 1 Sets the baud rate for the serial communication.
=1: 1200 bps
=3: 4800 bps
=5: 19200 bps
=2: 2400 bps
=4: 9600 bps
=6: 38400 bps
C402
Station Number 1 1 247 1 Sets the station number (address).
C403
Parity 1 1 3 1 Setting the parity requirement for the
communication
=1: No Parity
=2: Odd parity
=3: Even Parity
C404
Response Time Sec 0.01 0.00 2.00 0.01 Set the minimum time from receiving the
command to returning an answer.
C405
Operation Panel
Communication
Loss Selection
0 0 1 1 Enable or disable the operation panel
communication loss fault. If enabled, AC DRIVE
will generate fault if it does not receive any
response from the operation panel within
100msec.
=0: Disable
=1: Enable
GROUP
-
5: AUTO RESTART & SPEED SEARCH FUNCTION
C501
No. Of Restart 0 0 10 1 Sets the number of restart for ten faults.
C502
Restart Wait Time Sec 5 1 30 1 Sets the wait time before auto restart.
C503
Emergency Stop
Mode
1 1 3 1 Set the stopping method for the emergency
stop.
=1: Coast to stop without fault output
=2: Coast to stop with fault output
=3: Ramp down to stop
C504
Speed Search
Selection
0 0 1 1 Enable or disable the speed Search operation.
=0: Disable
=1: Enable
C505
Speed Search
Current Limit
% 70 30 200 1 Sets the speed search operation current as a
percentage, taking the AC DRIVE rated current
as 100%. Not usually necessary to set. When
restarting is not possible with the factory
settings, reduce the value.
C506
Speed Search
Frequency
Deceleration Time
Sec 2.00 0.01 30.00 0.01 This decides the frequency ramp down time
from max frequency during speed search
operation.
C507
Speed Search
Voltage
Acceleration Time
Sec 2.0 0.1 10.0 0.1 This decides the output voltage ramp up time
from zero to base voltage during speed search
operation.
C508
Speed Search
Wait Time
Sec 2.0 0.0 20.0 0.1 The wait time after the output is cut off to when
the speed search operation is started is set. Set
the time to when the motor residual voltage is
abated for this parameter. The search operation
is delayed by the time set here.