FL 128 Multizone System 15.01.2021 28
Exception Codes
The comms module returns 3 exception codes if the command received is invalid and these are given in
the table below.
Exception Code
Description
1
Invalid start address (address greater than 57 decimal)
2
Invalid end address (no. Bytes too large, i.e. start address add number of bytes greater
that 58 decimal)
3
Stop Character missing
The 7th bit of the return start address is set to logic 1 if any exception is generated (see sample below).
QUERY
Field Name
Start character
Slave Address
Start address
No. bytes
Stop character
Example
(Hex)
3A
11
6C
05
3E
RESPONSE
Field Name
Start character
Slave Address
Start address
Exception code
Stop character
Example
(Hex)
3A
11
EC
01
3E