OptiMeOptiMe
2021/01 Rev. 0.4
6 / 38
Display Possible cause Solution
E5
BREWER ERROR
The problem can be caused by bad
contact sockets from the 2 and 4
pole Molex connectors. Check if
all the socket (male/female) make
contact with each other.
The connectors are to be found
behind the left panel.
The 2 pole Molex is responsible for
the motor signal 230Vac.
The 4 pole Molex is responsible
for the position switch signals (low
voltage).
E6
TEMPERATURE HOT
WATER BOILER TO
HIGH
Temperature sensor measures a
temperature over 105 °C.
The control has disabled the heater
output.
AISI 316L / 1.4404
O-ring 10,82 x 1,78mm
M12 x 1
HEX17
ww-yy
T (°C) R (Ohm) T (°C) R (Ohm)
0 334.000 70 16.874
10 201.660 75 14.198
20 125.470 80 11.998
25 100.000 85 10.181
30 80.223 90 8.674
40 52.589 95 7.419
45 42.951 100 6.369
50 35.272 120 3.581
55 29.119 140 2.117
60 24.161 160 1.307
65 20.144
NTC resistance table
Check the temperature sensor operation
in the service menu 2.07 Hardware test
/ inputs / temperature.
AISI 316L / 1.4404
O-ring 10,82 x 1,78mm
M12 x 1
HEX17
ww-yy
Boiler overheated, let the boiler cool
down.
Check whether the boil-dry protection
was activated. Reset if necessary.
Attention; the metal reset levers are LIVE!
145°C +/- 7,5K
10A / 230Vac
Reset