APC 1400VA XL - High Transfer Point Setting; Low Transfer Point Setting; Output Voltage Selection

APC 1400VA XL
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
High Transfer
Point
230V models:
253VAC
120V models:
132VAC
100V models:
110VAC
230V models:
264, 271,
280VAC
120V models:
129, 135,
138VAC
100V models:
108, 112,
114VAC
To avoid unnecessary battery usage, set
the high transfer point higher if the util-
ity voltage is chronically high and the
connected equipment is known to work
under this condition.
Low Transfer
Point
230V models:
196VAC
120V models:
103VAC
100V models:
90VAC
230V models:
188, 204,
208VAC
120V models:
97, 100, 106VAC
100V models:
81, 85, 92VAC
Set the low transfer point lower if the
utility voltage is chronically low and the
connected equipment can tolerate this
condition.
Output Voltage 230V models:
230VAC
230V models:
220, 225,
240VAC
230V models only; allow the user to se-
lect the output voltage.