9Smart-UPS Rack-Mount2U 750/1000/1500 VA 120/230 Vac, 3000 VA 100/120/208/230 Vac, 2200 VA 120 Vac
General Settings
Configure these settings at any time, using the display interface or PowerChute
software.
Function Factory Default Options Description
High Transfer
Point
100 Vac:
108 Vac
108 Vac
•110 Vac
•112 Vac
•114 Vac
To avoid unnecessary battery usage, set the transfer point
higher if the utility voltage is chronically high and the
connected equipment is known to work under this condition.
The
POWER QUALITY setting will automatically change this
setting.
Note: Use the Advanced Menus to configure this setting.
120 Vac:
127 Vac
127 Vac
130 Vac
133 Vac
136 Vac
208 Vac:
225 Vac
225 Vac
229 Vac
233 Vac
237 Vac
230 Vac:
253 Vac
253 Vac
257 Vac
261 Vac
265 Vac
Low Transfer
Point
100 Vac:
92 Vac
86 Vac
88 Vac
90 Vac
92 Vac
Set the transfer point lower if the utility voltage is
chronically low and the connected equipment can tolerate
this condition.This setting may also be adjusted using the
power quality setting.
Note: Use the Advanced Menus to configure this setting.
120 Vac:
106 Vac
97 Vac
100 Vac
103 Vac
106 Vac
208 Vac:
182 Vac
170 Vac
174 Vac
178 Vac
182 Vac
230 Vac:
208 Vac
196 Vac
200 Vac
204 Vac
208 Vac
Nominal Output
Voltage
100 Vac N/A
Set the nominal output voltage of the UPS on battery. This is
available on 230 Vac models only.
120 Vac N/A
230 Vac 208-252 Vac
Transfer
Sensitivity
High High, Reduced, Low
Select the level of sensitivity to power events that the UPS
will tolerate.
High: The UPS will go on battery power more often to
provide the cleanest power supply to the connected
equipment.
Low: The UPS will tolerate more fluctuations in power and
will go on battery power less often.
If the connected load is sensitive to power disturbances, set
the sensitivity to High.
Low Battery
Warning
120 sec
Set the value in
seconds
The UPS will emit an audible alarm when the remaining
runtime has reached this level.