Do you have a question about the APC BACK-UPS ES 500 and is the answer not in the manual?
Procedure to disconnect and reconnect the internal battery for the Back-UPS unit.
Guidelines for positioning the Back-UPS to avoid direct sunlight, excessive heat, humidity, or fluids.
Details on connecting devices to Battery Back Up and Surge Only outlets on the Back-UPS.
Instructions for connecting a phone line to the Back-UPS for surge protection.
Procedure to power on the Back-UPS and recommended charging time before use.
Optional steps for connecting the Back-UPS via USB and installing management software.
Green indicator signifies facility power is active and supplying the Battery Backup outlets.
Yellow indicator lights up when the Back-UPS is supplying power from its battery.
Explanation of various audible alarms: single beep, four beeps, continuous beeping, and 1-minute beeps.
Red indicator signals the battery is nearing end-of-life or not properly connected.
Red indicator shows when connected load exceeds Back-UPS capacity or Battery Backup outlets are overloaded.
Location and function of the circuit breaker button, which trips during overload conditions.
Step-by-step guide for safely removing and replacing the internal battery of the Back-UPS.
Procedure to adjust the Back-UPS transfer voltage sensitivity for optimal performance.
Troubleshooting steps for when the Back-UPS fails to power on, checking connections and breakers.
Procedure to reset the circuit breaker and identify causes of repeated tripping.
Diagnosing and resolving issues related to insufficient input voltage from the power source.
Troubleshooting why the Back-UPS fails to provide power to connected equipment during an outage.
Steps to resolve instances where the Back-UPS switches to battery power unnecessarily.
Identifying reasons for shorter than expected backup time, such as overload or battery condition.
Troubleshooting steps when the 'Replace Battery' indicator is illuminated.
Resolving overload conditions indicated by the Back-UPS.
Actions to take when the 'Replace Battery' indicator flashes, suggesting a unit failure.
Instructions on how to obtain service for the Back-UPS, including troubleshooting and contacting APC.
Step-by-step guide for mounting the Back-UPS unit vertically or horizontally on a wall surface.
Procedure to disconnect and reconnect the internal battery for the Back-UPS unit.
Guidelines for positioning the Back-UPS to avoid direct sunlight, excessive heat, humidity, or fluids.
Details on connecting devices to Battery Back Up and Surge Only outlets on the Back-UPS.
Instructions for connecting a phone line to the Back-UPS for surge protection.
Procedure to power on the Back-UPS and recommended charging time before use.
Optional steps for connecting the Back-UPS via USB and installing management software.
Green indicator signifies facility power is active and supplying the Battery Backup outlets.
Yellow indicator lights up when the Back-UPS is supplying power from its battery.
Explanation of various audible alarms: single beep, four beeps, continuous beeping, and 1-minute beeps.
Red indicator signals the battery is nearing end-of-life or not properly connected.
Red indicator shows when connected load exceeds Back-UPS capacity or Battery Backup outlets are overloaded.
Location and function of the circuit breaker button, which trips during overload conditions.
Step-by-step guide for safely removing and replacing the internal battery of the Back-UPS.
Procedure to adjust the Back-UPS transfer voltage sensitivity for optimal performance.
Troubleshooting steps for when the Back-UPS fails to power on, checking connections and breakers.
Procedure to reset the circuit breaker and identify causes of repeated tripping.
Diagnosing and resolving issues related to insufficient input voltage from the power source.
Troubleshooting why the Back-UPS fails to provide power to connected equipment during an outage.
Steps to resolve instances where the Back-UPS switches to battery power unnecessarily.
Identifying reasons for shorter than expected backup time, such as overload or battery condition.
Troubleshooting steps when the 'Replace Battery' indicator is illuminated.
Resolving overload conditions indicated by the Back-UPS.
Actions to take when the 'Replace Battery' indicator flashes, suggesting a unit failure.
Instructions on how to obtain service for the Back-UPS, including troubleshooting and contacting APC.
Step-by-step guide for mounting the Back-UPS unit vertically or horizontally on a wall surface.
| Output Power Capacity | 300 Watts / 500 VA |
|---|---|
| Nominal Output Voltage | 230V |
| Topology | Standby |
| Waveform Type | Stepped approximation to a sinewave |
| Input Voltage | 230V |
| Transfer Time | 6 ms typical: 10 ms maximum |
| Input Frequency | 50/60 Hz +/- 3 Hz (auto sensing) |
| Output Frequency (sync to mains) | 50/60 Hz +/- 1 Hz |
| Input Connections | IEC-320 C14 |
| Surge energy rating | 310 Joules |
| Operating Temperature | 0 - 40 °C |
| Operating Altitude | 0-3000 meters |
| Storage Temperature | -15 - 45 °C |
| Storage Altitude | 0-15000 meters |
| Battery Type | Lead-acid battery |
| Typical Recharge Time | 16 hours |
| Output Connections | IEC 320 C13 |
| Control panel | LED status display with On Line |
| Audible Alarm | Alarm when on battery: distinctive low battery alarm |
| Operating Relative Humidity | 0 - 95% non-condensing |
| Storage Relative Humidity | 0 - 95% non-condensing |
| Filtering | Full time multi-pole noise filtering: 5% IEEE surge let-through: zero clamping response time: meets UL 1449 |
Loading...