Back-UPS
350/500
User Manual
EN 990-9230A 06/2013
Inventory
1
Connect the Battery
3
Check the Building
Wiring Fault Indicator
4
Connect Equipment
6
Switch On the
Back-UPS
In compliance with Department of Transportation (DOT) regulations, the Back-UPS is shipped with the
internal red battery wire disconnected. The Back-UPS will not operate until the internal red wire is
connected to the battery. Once connected, allow the Back-UPS to charge for a full eight hours prior
to use.
Note: Small sparks may occur during battery connection. This is normal.
a. Open the battery compartment, as shown.
b. Pull the battery about half way out, as
shown.
c. Connect the red battery wire to the positive
battery terminal.
d. Push the battery into the battery compartment
and re-install the cover, as shown.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in
contact with fluids, or where there is excessive
dust or humidity.
Be sure the air vents on the UPS are not blocked.
Allow adequate space for proper ventilation.
The battery typically lasts for two to three years.
Environmental factors impact battery life. Elevated
ambient temperatures, poor quality AC power, and
frequent short duration discharges will shorten
battery life.
Connect the UPS power cable directly to a wall
outlet. Do not use surge protectors or extension
cords.
Plug the Back-UPS into a wall outlet, as shown.
If the red Building Wiring Fault indicator on the
rear panel of the Back-UPS is lit, one of the
following conditions exists:
• Open or high resistance ground
• Hot or neutral polarity reversed
• Overloaded neutral circuit
A lit indicator means that a potential shock
hazard exists. Improper building wiring should
be corrected by a qualified electrician. Do not
use the Back-UPS until the condition that
caused the fault is corrected.
Note: Improper building wiring will not prevent
the Back-UPS from operating, but it will limit its
protection capability. It may also result in
equipment damage that is not covered by the APC
by Schneider Electric Equipment Protection
Policy.
The rear panel of the Back-UPS consists of the
following elements:
Battery Back Up Outlets (qty. of 3). These
outlets provide battery back-up, surge protection,
and Electro-magnetic Interference (EMI)
filtering. In case of power outage, battery power
is automatically provided to these outlets. Power
(AC or battery) is not supplied to these outlets
when the Back-UPS is switched Off. Connect a
computer, monitor, and external disk or CD-
ROM drive to these outlets.
External
Drive
Computer
Monitor
Scanner
Printer
Fax
Note: Allow the Back-UPS to charge for a full eight
hours prior to use.
Press the push-button on the front panel of the
Back-UPS.
Observe that the following events occur after press-
ing and releasing the push-button:
The green On-Line indicator flashes.
The yellow On Battery indicator lights while
the Self-Test is being performed.
When Self-Test has successfully completed,
only the green On Line indicator will be lit.
If the internal battery is not connected, (see
Step 1 above) the green On Line indicator and
red Replace Battery indicator will light. The
Back-UPS will also emit a chirping sound.
On Line
On Battery
Overload
Replace Battery
7
There are four status indicators (lights) on the front
panel of the Back-UPS (On Line, On Battery,
Overload, and Replace Battery).
On Line (green) - is lit whenever AC power is
powering the Battery Backup outlets.
On Line
On Battery
Overload
Replace Battery
Overload (red) - is lit whenever power
demand has exceeded the capacity of the Back-
UPS.
Continuous Tone - this alarm is
sounded whenever the Battery
Backup outlets are overloaded.
Circuit Breaker - the circuit
breaker button located on the rear
panel of the Back-UPS will stick
out if an overload condition forces
the Back-UPS to disconnect itself
from AC power. If the button
sticks out, disconnect non-
essential equipment. Reset the
circuit breaker by pushing the
button inward.
5
Connect the Phone
Line to Surge Protection
The telephone ports provide lightning surge pro-
tection for any device connected to the telephone
line (computer, modem, fax or telephone). The
telephone ports are compatible with Home Phone-
line Networking Alliance (HPNA) and Digital
Subscriber Line (DSL) standards, as well as all
modem data rates. Connect as shown.
Wall Outlet
Modem/Phone/Fax
Replace Battery (red) - is lit whenever the
battery is near the end of its useful life, or if
the battery is not connected (see above). A
battery that is near the end of its useful life has
insufficient run-time and should be replaced.
Chirps for 1 Minute Every 5
Hours - this alarm is sounded
whenever the battery has failed the
automatic diagnostic test.
CS
TO COMPUTER
USB PORT
RJ-45 to USB
CABLE
Connect USB Cable
and Install Software
(optional)
NOTE: Macintosh Users - for full USB perfor-
mance, use OS 10.1.5 or higher.
If Autoplay is not enabled on the computer, proceed
as follows:
1. On the computer desktop of the display, double-
click on My Computer.
2. Double-click on the CD-ROM drive icon and
follow the on-screen instructions.
Follow the
on-screen
instructions.
Status Indicators and Alarms
In situations where the Back-UPS or connected equipment appears too sensitive to input voltage, it may be
necessary to adjust the transfer voltage. This is a simple task requiring use of the front panel push button. To
adjust the transfer voltage, proceed as follows:
1.Plug the Back-UPS into the AC power source. The Back-UPS will be in a Standby Mode (no indicators
lit).
2.Press the front panel push button fully inward for 10 seconds. All indicators on the Back-UPS will flash to
acknowledge going into Programming Mode.
3.The Back-UPS will then indicate its current Sensitivity Setting, as shown in the following table.
4.To select the Low Sensitivity setting, press the push button until the yellow indicator is flashing.
5.To select the Medium Sensitivity setting, press the push button until the yellow and red indicators (second
and third from the top) are flashing.
6.To select the High Sensitivity setting, press the push button until yellow and both red indicators (bottom
three) are flashing.
7.To exit without changing the Sensitivity Setting, press the push button until the green indicator is flashing.
8.Once in Programming Mode, if the push button is not pressed within 5 seconds, the Back-UPS will exit
Programming Mode; all indicators will extinguish.
Indicators
Flashing
Sensitivity
Setting
Input Voltage
Range
(for AC
operation)
Use When
1
(yellow)
Low 88 - 142 Vac Input voltage is extremely low or high.
Not recommended for computer loads.
2
(yellow, and
red)
Medium
(factory default)
92 - 139 Vac Back-UPS frequently goes On Battery.
3
(yellow, red,
and red)
High 96 - 136 Vac Connected equipment is sensitive to
voltage fluctuations (recommended).
On Battery (yellow) - is lit whenever the bat-
tery of the Back-UPS is powering equipment con-
nected to the Battery Backup Outlets.
Four Beeps Every 30 Seconds - this
alarm is sounded whenever the Back-
UPS is running On Battery. Consider
saving work in progress.
Continuous Beeping - this alarm is
sounded whenever a low battery con-
dition is reached. Battery run-time is
very low. Promptly save any work in
progress and exit all open applica-
tions. Shutdown the operating sys-
tem, computer and the Back-UPS.
Transfer Voltage and Sensitivity Adjustment (optional)
Surge Only Outlets (qty. of 3). These outlets are
always On (when AC power is available) and are
not controlled by the On/Off switch. These outlets
do not provide power during a power outage. Con-
nect a printer, fax machine or scanner to these out-
lets
Black Velcro Straps (qty. of 2 - not shown). For
convenience, two velcro traps have been included
and can be used to manage power cords.
to the Back-UPS
2
Placement / Power
Installation
Inspect the package contents
upon receipt. Notify the
carrier and dealer if there is
any damage.
Read the Safety Guide supplied with this
unit before installing the UPS.
© 2013 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by
Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks
are property of their respective owners.
Safety and General
Information
User Documentation
Question and Answer IconNeed help?

Do you have a question about the APC Back-UPS CS 350 and is the answer not in the manual?

APC Back-UPS CS 350 Specifications

General IconGeneral
Input Voltage230V
Output Voltage230V
Number of Outlets4
TopologyStandby
Waveform TypeStepped approximation to a sinewave
Frequency50/60 Hz
Power Rating350 VA
Output Power Capacity210 W
Battery TypeSealed lead-acid battery (maintenance-free)
Input Frequency50/60 Hz
Output Frequency (sync to mains)50/60 Hz
Transfer Time6 ms typical : 10 ms maximum
Control panelLED indicators
Audible AlarmYes
FilteringFull-time multi-pole noise filtering
Number of Outlets TypeIEC 320 C13

Summary

Installation

Connect the Battery

Connects the internal red battery wire to the positive battery terminal. Allows operation after charging.

Placement and Power Connection

Provides guidelines for optimal UPS placement and power connection to a wall outlet.

Building Wiring Fault Indicator

Checks for building wiring faults indicated by a red light and potential shock hazards.

Connecting Equipment

Details connecting devices to Surge Only and Battery Back Up outlets.

Phone Line Surge Protection

Connects phone lines to the UPS for lightning surge protection.

Powering On the UPS

Instructions on powering on the Back-UPS unit and observing initial indicators.

USB Cable and Software Installation

Guides connecting the USB cable and installing management software for enhanced functionality.

Safety and General Information

Package Inspection

Instructions to inspect package contents upon receipt and notify carrier if damaged.

Read Safety Guide

Emphasizes reading the supplied Safety Guide before installing the UPS.

Status Indicators and Alarms

Front Panel Indicators

Describes the meaning of On Line, On Battery, Overload, and Replace Battery indicators.

Audible Alarms

Explains various audible alarms like beeps, continuous beeping, and chirps.

Circuit Breaker Reset

Details the circuit breaker button function and reset procedure for overload conditions.

Transfer Voltage and Sensitivity Adjustment

Entering Programming Mode

Enter programming mode by pressing the push button for 10 seconds.

Adjusting Sensitivity Settings

Adjust sensitivity (Low, Medium, High) using the front panel push button.

Exiting Programming Mode

Exit programming mode by pressing the push button until green indicator flashes or timeout.

Troubleshooting Common Issues

UPS Not Switching On

Troubleshoots issues where the Back-UPS fails to power on due to connection or breaker problems.

Circuit Breaker Tripped

Guides on resetting the circuit breaker and identifying overload causes.

Low AC Voltage Problems

Addresses issues related to insufficient AC voltage and recommends electrician checks.

Backup Power Failure

Troubleshoots why the UPS does not provide backup power, checking battery and outlet connections.

UPS Operates on Battery

Diagnoses UPS operating on battery during normal AC, checking for breaker trips or wiring issues.

Reduced Backup Time

Addresses reduced backup time due to overload, battery charge, or battery age.

Interpreting Red Indicators

Explains meanings of lit red indicators for battery, overload, and potential faults.

Flashing Red Indicators

Indicates a critical Back-UPS failure requiring technical support.

Battery Replacement Indicator;Alarm

Diagnoses the 'Replace Battery' indicator and alarm, often due to disconnected or old batteries.

Back-UPS Storage and Maintenance

Storage Recommendations

Provides guidelines for storing the Back-UPS, including charging and temperature.

Order Replacement Battery

Details how to order a replacement battery, specifying model RBC2.

Battery Replacement Procedure

Details the process of safely replacing the internal battery, including steps and precautions.

Service and Support

Obtaining Service

Outlines steps for obtaining service, including contacting support and preparing the unit.

Product Warranty

Details the standard two-year warranty, replacement procedures, and customer responsibilities.

Customer Support Contact

Information on how to find country-specific customer support via the APC website.

EMI Compliance and Regulatory Information

EMI Compliance Certification

States compliance with FCC/DOC Class B standards for digital devices and interference.

Correcting Interference

Provides measures to correct harmful interference to radio or television reception.

Telephone Connection Regulations

Provides FCC registration number and Ringer Equivalence Number (REN) for telephone connections.