EasyManua.ls Logo

Apollo Seiko OMEGA - Page 44

Apollo Seiko OMEGA
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 / 60
13.10.5 IRON UNIT ERROR Operation (Sensor Error)
1. When it performs control for rising or lowering the iron, if the operation does not complete within
the time is set by iron up / down sensor error limit, it becomes sensor error.
2. When sensor error occurs, it stops soldering.
3. When sensor error occurs, IRON UNIT ERROR signal becomes Low.
4. When sensor error occurs, RUNNING signal becomes Low.
5. When sensor error occurs, END signal is outputted.
6. When it detects RESET signal, READY signal becomes High.
7. When READY signal becomes High, it is possible to start the operation by START signal.
When sensor error occurs, the temperature control function becomes OFF.
When READY signal become High, it starts to control the temperature again.
* It is not necessary that START signal is outputted as a pulse. (Except for LAN operation)
Input
Output