EasyManua.ls Logo

Applied Motion Products STAC6 Series - Page 51

Applied Motion Products STAC6 Series
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
STAC6 Hardware manual
920-0029 Rev. B
11/19/2010
INPUTS AND OUTPUTS
IN / OUT 1 connector - All Drives
7 Inputs
X1, X2 Optically Isolated, Differential, 5 Volt. Minimum pulse width = 250ns. Maximum pulse,
frequency = 2 MHz
Function: Step & Direction, Encoder Following, Sensor, Home or Branch Select
X3 Optically isolated, 12 - 24V, sourcing or sinking. Function: Motor Enable, Sensor, Home
or Branch Select. X3 - X7 have shared common.
X4 Optically isolated, 12 - 24V, sourcing or sinking. Function: Alarm Reset, Sensor, Home or
Branch Select. X3 - X7 have shared common.
X5 Optically isolated, 12 - 24V. Function. Function; general Purpose Input. X3 - X7 have
shared common.
X6,X7 Optically isolated, 12 - 24V. Function: CW & CCW Limits, Sensor, Home or Branch Select.
X3 - X7 have shared common.
3 Outputs
Y1 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y2 & Y3.
Function: Brake or general purpose programmable
Y2 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y1 & Y3.
Function: Motion, tach or general purpose programmable
Y3 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y1 & Y2.
Function: Fault or general purpose programmable
Analog Inputs
Software selectable: 0-5V, ±5V, 0-10V, ±10V,
RESOLUTION 12 bits (with ±10V signal range)
11 bits (with 0-10V or ±5V signal range)
10 bits (with 0-5V signal range)
IN / OUT 2 connector - QE and Si
8 Digital Inputs
IN1-IN6 Optically isolated, 12 - 24V. Function. Function; general Purpose Input. Shared common.
IN7,IN8 Optically isolated, differential. 12 - 24V. Function; general Purpose Input.
4 Digital Outputs
OUT 1-4 Optical darlington, 30V, 100mA max, sinking or sourcing. Function: general purpose
programmable
1 Analog Input 0-5VDC analog input - for use with Q or SCL applications only