Operation Instructions
16
Commissioning Parameters Setting
No Full Name Display Name Range Default Remark
1 T-HP max T-HP max 40~55 °C 104~131°C 50/122°C
2 Cool run time Cool run time 1~10min
3min
[2-way valve Off]
5min
[2-way valve On]
3 Heat run time Heat run time 1~10min
3min
[2-way valve Off]
5min
[2-way valve On]
2.4.1 Ctrl. state
[Operation Instructions]
At the commissioning parameter setting page, by touching “Ctrl. state”, it can be set to “T-water out” or “T-room”
[Notes]
When “Remote sensor” is set to “With”, this setting can be set to “T-water out” or “T-room”. When “Remote
sensor” is set to “Without”, this setting can only be set to “T-water out”.
This setting will be memorized upon power failure.