EasyManua.ls Logo

ARIS ExTensor - Page 27

ARIS ExTensor
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27ExTensor
ADVICE
!
Feedback of block detection via relay (Setting 6 & 7)
The condition of the block detection can be put out via relay 3 and 4. Therefore, the settings for block detection are
matched to the preferred relay in the relay settings menu. The block detection feedback can differ between block
detection in left end position and block detection in right end position. On a block detection within the set range, the
relay will switch.
EXPT. MENU (Expert menu)
Signal IN Input signal
Selection of input signal type for controlling the actuator.
The following control features are available (depending on the activated features):
Term. 2/3 (Terminal 2/3): Driving the actuator via terminal 2/3.
Ctrl. [mA] (Control [mA], i-Act): Driving the actuator by feeding a set value signal in range 0...20 mA.
Ctrl. [V] (Control [V], i-Act): Driving the actuator by feeding a set value signal in range 0...10 V.
Poti (Potentiometer, i-Act): Driving the actuator via a connected external potentiometer.
The input signal type must additionally be set up with the onboard DIP switch, according to the desired signal type.
DIP switch 1 and DIP switch 2 must not be active (On) simultaneous!
DIP switch 4 and DIP switch 5 must not be active (On) simultaneous!
Relay switching state
1 (switched on/active)
0 (switched off/inactive)
left
end position
right
end position
[7] Bl.det.ri
Blockade at
right end position

Related product manuals