Electromagnetic Flowmeter M-910
36
Operation manual
Impulse output mode setting
SPM(?)<CPD> { 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 }
Following modes can be set:
0 Off
1 Pos.Flow
2 Neg.Flow
3 Bip.Flow
4 On Pos.
5 On Neg.
6 On In
7 On Out
8 Dose On
9 Dose Off
10 On>F1
11 On<F1
M910 confirms execution with string „Ok<cr>”.
Example RS232:
Command „SPM1<cr>” sets mode “Positive flowrate” for impulse output. If query „SPM?<cr>” is sent, flowmeter
returns response in format „1<cr>”.
Status output mode setting
SSM(?)<CPD> { 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 }
Following modes can be set:
0 Off
1 On Pos.
2 On Neg.
3 On In
4 On Out
5 Dose On
6 Dose Off
7 On>F1
8 On<F1
M910 confirms execution with string „Ok<cr>”.
Example:
Command „SSM1<cr>” sets mode “On for positive flowrate” for status output. If query „SSM?<cr>” is sent,
flowmeter returns response in format „1<cr>”.
Digital input mode setting
SIM(?)<CPD> { 0 | 1 | 2 }
Following modes can be set:
0 Off
1 Dose
2 Clr.Vol
M910 confirms execution with string „Ok<cr>”.
Example: