Electromagnetic flowmeter M910
Operation manual
37
Command „SIM1<cr>” sets mode “Dose” for digital input. If query „SIM?<cr>” is sent, flowmeter returns
response in format „1<cr>”.
Current output constant QI
SCO(?)<DNPD>
Command sets constant QI, which represents flowrate value for current 20 mA.
<DNPD>
It represents required flowrate in actual units. M910 confirms execution with string „Ok<cr>”. In case of query
M910 returns set value in actual units.
Example:
Command „SCO10.5<cr>” sets value QI to 10.5 in actual units. After query „SCO?<cr>” flowmeter returns string
„10.500000<cr>”.
Frequency output constant QF
SFO(?)<DNPD>
Command sets constant QF, which represents flowrate value for frequency 1000 Hz.
<DNPD>
It represents required flowrate in actual units. M910 confirms execution with string „Ok<cr>”. In case of query
M910 returns set value in actual units.
Example:
Command „SFO10.5<cr>” sets value QF to 10.5. After query „SFO?<cr>” flowmeter returns string
„10.500000<cr>”.
Impulse output constant QP
SPO(?)<DNPD>
Command sets constant QP, which represents volume for 1 impulse.
<DNPD>
It represents volume for 1 impulse in actual units. M910 confirms execution with string „Ok<cr>”. In case of query
M910 returns set value in actual units.
Example:
Command „SPO1.0<cr>” sets value QP to 1.0. After query „SPO?<cr>” flowmeter returns string „1.000000<cr>”.
Dosing constant QD
SIO(?)<DNPD>
Command sets constant QD, which represents volume for dosing.
<DNPD>
It represents volume for dosing in actual units. M910 confirms execution with string „Ok<cr>”. In case of query
M910 returns set value in actual units.
Example:
Command „SIO1.0<cr>” sets value QD to 1.0. After query „SIO?<cr>” flowmeter returns string „1.000000<cr>”.
Impulse width
SPT(?)<DNPD>