EasyManua.ls Logo

Armstrong 4000 - Clock Setup Configuration; Bypass Valve Setup Configuration

Armstrong 4000
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
installation &
operating instructions
ips 4000 controller - Integrated pumping
system for variable primary applications
19
4.1.9 clock setup
Parameter: hh
Range: Function:
0 - 24 Sytem clock hour
Parameter: mm
Range: Function:
0 - 60 Sytem clock minute
Parameter: dd
Range: Function:
1 - 31 Sytem clock day
Parameter: mm
Range: Function:
1 - 12 Sytem clock month
Parameter: yy
Range: Function:
00 – 99 Sytem clock year
4.1.10 bypass valve setup
Parameter: Kc
Range: Function:
0-9999 Determines the valve control pid loop gain. Smaller
values correspond to a more responsive controller
Parameter: Ti
Range: Function:
0-999 Determines the valve control pid loop integral time.
Larger values correspond to more iterations and
reduction of steady state error
Parameter: valve output
Options: Function:
0 – 10 vdc 0 vdc commands the valve as fully closed. 10 vdc as
fully open
2 – 10 vdc 2 vdc commands the valve as fully closed. 10 vdc as
fully open
Parameter: minimum position
Range: Function:
0.0 - 100.0 Minimum position the valve is allowed to
Parameter: maximum position
Range: Function:
0.0 - 100.0 Maximum position the valve is allowed to
Parameter: open setpoint
Range: Function:
0.0 - 100.0 When system flow is under the chiller/boiler
minimum and the bypass valve is open at this
percentage (or above), the pumps will ramp up to
maximum speed
Parameter: close setpoint
Range: Function:
0.0 - 100.0 When the system flow is under the chiller/boiler
minimum and the bypass valve is closing and
reaches this percentage (or below) the pumps
return to their normal speed

Related product manuals