installation &
operating instructions
ips 4000 controller - Integrated pumping
system for variable primary applications
20
Button: save
Range: Function:
n/a Saves current parameters as default. Only available
in level 2
Button: restore
Range: Function:
n/a Restores default parameters. Only available in levels
1 & 2
4.1.11 bas communication setup
Parameter: protocol
Options: Function:
n/a No bas protocol is selected
Modbus Selects Modbus rtu
Lonworks Selects Lonworks
BACnet Selects BACnet
Parameter: address
Range: Function:
0-127 Selects the ips bas address. Only applies to Modbus
protocol
Parameter: baud rate
Options: Function:
1200 Selects 1200 as baud rate. Only applies to Modbus
protocol
2400 Selects 2400 as baud rate. Only applies to Modbus
protocol
4800 Selects 4800 as baud rate. Only applies to Modbus
protocol
9600 Selects 9600 as baud rate. Only applies to Modbus
protocol
19200 Selects 19200 as baud rate. Only applies to Modbus
protocol
Button: save
Range: Function:
n/a Saves current parameters as default. Only available
in level 2
Button: restore
Range: Function:
n/a Restores default parameters. Only available in levels
1 & 2