PCB Errors (Terminal)
PCB Errors (Recoverable)
The following errors indicate the PCB has failed, but
may be recoverable. Turn power o for 10 seconds and
restart. If the error persists, replace the Front Cover
Assembly with PCBA.
P/N - D112643 Front Cover Assembly with PCBA
see pages 33-34.
• A2D timeout
• RAM error
• Real time check error
• Flash error
• Algorithm error
• Controller fault
• Stack error
• Scheduling error
• Capacitive touch sensor error
The following errors indicate the PCB has failed.
Replace the Front Cover Assembly with PCBA.
P/N - D112643 Front Cover Assembly with PCBA
see pages 33-34.
• Uncongured error
• A2D range error
• General A2D error
• EEPROM error