Ascon Tecnologic - K Series - ENGINEERING MANUAL - PAG. 33
]
PrG Group (Programmer Function Parameters)
no.
Para-
meter
Description Dec. Range Default
Vis.
Promo.
89 Pr.F Program action at power ON 0
nonE Programmer not used
S.uP.d Start at power ON, first step in stand-by
S.uP.S Start at power ON
u.diG Start at Run command detection only
u.dG.d Start at Run command
, first step in stand-by
nonE A-67
90 Pr.u Engineering unit of the soak 2
hh.nn Hours and minutes
nn.SS Minutes and seconds
hh.nn A-68
91 Pr.E
Instrument behaviour at the end of
the program execution
0
cnt Continue
SPAt Go to the set point selected by SPAt
St.by Go to stand-by mode
SPAt A-71
92 Pr.Et Time of the end program indication 2
0 Function not used
0.01... 99.99 minutes and seconds
inF Indefinitely ON
oFF A-72
93 Pr.S1 Set point of the first soak dP From SPLL to SPHL 0 A-73
94 Pr.G1 Gradient of the first ramp 1
0.1... 999.9 Eng. Unit/minute
inF Step transfer
inF A-74
95 Pr.t1 Time of the first soak 2 0.00... 99.59 0.10 A-75
96 Pr.b1 Wait band of the first soak dP
0 oFF (no wait band)
1... 9999 (E.U.)
oFF A-76
97 Pr.E1 Events of the first group 2 00.00... 11.11 00.00 C-0
98 Pr.S2 Set point of the second soak dP OFF or from SPLL to SPHL 0 A-78
99 Pr.G2 Gradient of the second ramp 1
0.1... 999.9 Eng. Unit/minute
inF Step transfer
inF A-79
100 Pr.t2 Time of the second soak 2 0.00... 99.59 0.10 A-80
101 Pr.b2 Wait band of the second soak dP
0 oFF (no wait band)
1... 9999 (E.U.)
oFF A-81
102 Pr.E2 Events of the second group 2. 00.00... 11.11 00.00 C-0
103 Pr.S3 Set point of the third soak dP OFF or from SPLL to SPHL 0 A-83
104 Pr.G3 Gradient of the third ramp 1
0.1... 999.9 Eng. Unit/minute
inF Step transfer
inF A-84
105 Pr.t3 Time of the third soak 2 0.00... 99.59 0.10 A-85
106 Pr.b3 Wait band of the third soak dP
0 oFF (no wait band)
1... 9999 (E.U.)
oFF A-86
107 Pr.E3 Events of the third group 0 00.00... 11.11 00.00 C-0
108 Pr.S4 Set point of the fourth soak dP OFF or from SPLL to SPHL 0 A-88
109 Pr.G4 Gradient of the fourth ramp 1
0.1... 999.9 Eng. Unit/minute
inF Step transfer
inF A-89
110 Pr.t4 Time of the fourth soak 2 0.00... 99.59 0.10 A-90
111 Pr.b4 Wait band of the fourth soak dP
0 oFF (no wait band)
1... 9999 (E.U.)
oFF A-91
112 Pr.E4 Events of the fourth group 0 00.00... 11.11 00.00 C-0
113 Pr.St Program status 0
rES Program reset
run Program start
HoLd Program hold
0 C-0