Ascon Tecnologic - K Series - ENGINEERING MANUAL -Vr. 9.0 PAG. 30
]
AL1 Group (Alarm 1 Parameters)
no.
Para-
meter
Description Dec. Range Default
Vis.
Promo.
24 AL1t Alarm 1 type 0
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdE = Relative band alarm
LoAb A-47
25 Ab1 Alarm 1 function 0
0... 15
+1 = Not active at power ON
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
0 C-0
26 AL1L
- For High and low alarms, it is the
low limit of the AL1 threshold
- For band alarm, it is low alarm th-
reshold
dP From -1999 to AL1H ( E.U.) -1999 A-48
27 AL1H
- For High and low alarms, it is the
high limit of the AL1 threshold
- For band alarm, it is high alarm
threshold
dP From AL1L to 9999 ( E.U.) 9999 A-49
28 AL1 AL1 threshold dP From AL1L to AL1H (E.U.) 0 A-50
29 HAL1 AL1 hysteresis dP 1... 9999 (E.U.) 1 A-51
30 AL1d AL1 delay dP From 0 (oFF) to 9999 (s) oFF C-0
31 AL1o
Alarm 1 enabling during Stand-by
mode
0
0 = Never
1 = During stand by
2 = During overrange and underrange
3 = During overrange, underrange and stand-by
no C-0
]
AL2 Group (Alarm 2 Parameters)
no.
Para-
meter
Description Dec. Range Default
Vis.
Promo.
32 AL2t Alarm 2 type 0
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdE = Relative band alarm
HiAb A-54
33 Ab2 Alarm 2 function 0
0... 15
+1 = Not active at power ON
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
0 C-0
34 AL2L
- For High and low alarms, it is the
low limit of the AL2 threshold
- For band alarm, it is low alarm th-
reshold
dP From -1999 to AL2H (E.U.) -1999 A-56
35 AL2H
- For High and low alarms, it is the
high limit of the AL2 threshold
- For band alarm, it is high alarm
threshold
dP From AL2L to 9999 (E.U.) 9999 A-57
36 AL2 Alarm 2 threshold dP From AL2L to AL2H (E.U.) 0 A-58
37 HAL2 Alarm 2 hysteresis dP 1... 9999 (E.U.) 1 A-59
38 AL2d Alarm 2 delay dP From 0 (oFF) to 9999 (s) oFF C-0
39 AL2o
Alarm 2 enabling during Stand-by
mode
0
0 = Never
1 = During stand by
2 = During overrange and underrange
3 = During overrange, underrange and stand-by
no C-0