Ascon Tecnologic - Y39 Line - Operating Instructions - Pag. 14
“P” - Compressor protection and power on delay parameters
Parameter Description Range Default
40
P.P1
Output ot activation delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
41
P.P2
Delay after output ot switch off
oF/.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
42
P.P3
Minimum time between two output ot power on
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
43
P.od
Delay outputs activation at power on oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
“A” - Alarm parameters
Parameter Description Range Default
44
A.Ay
Temperature alarms type
1 Absolute to Pr1, label (Hi-Lo);
2 Relative to Pr1, label (Hi-Lo);
3 Absolute to Au, label (Hi-Lo);
4 Relative to Au, label (Hi-Lo);
5 Absolute to Pr1, no label;
6 Relative to Pr1, no label;
7 Absolute to Au no label;
8 Relative to Au, no label.
1
45
A.HA
High temperature Alarm threshold oF/-99.9 ÷ +999°C/°F oF
46
A.LA
Low
temperature
Alarm threshold
oF/-99.9 ÷ +999°C/°F oF
47
A.Ad
Temperature
Alarms Differential
0 ÷ 30°C/°F 1.0
48
A.At
Temperature Alarms delay oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
49
A.tA
Alarm memory oF/on oF
50
A.PA
Temperature Alarms delay at power ON
oF/0.01 ÷ 9.59 (h.min)
÷ 99.5 (h.min
x 10
) 2.00
51
A.dA
Temp. Alarms delay after defrost and continuous cycle
and unlock display delay after defrost
oF/0.01 ÷ 9.59 (h.min)
÷ 99.5 (h.min
x 10
) 1.00
52
A.oA
Alarm delay with door open oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) 3.00
“o” - Outputs and buzzer configuration parameters
Parameter Description Range Default
53
o.o1
OUT1 function
oF No function;
ot Temp. Control (compressor);
dF Defrosting;
Fn Fan;
Au Auxiliary;
At Silenceable alarm;
AL Not silenceable Alarm;
An Stored alarm;
on
On when instrument switched on.
ot
54
o.o2
OUT2 function dF
55
o.o3
OUT3 function Fn
56
o.bu
Buzzer function mode
oF Disable;
1 Active alarms only;
2 Key pressed only;
3 Active alarms and key pressed.
3
57
o.Fo
Function mode auxiliary output
oF No Function;
1 Control output ot delayed;
2 Manual activation by key or digital input;
3
Light with eco mode (ON with SP, OFF with SP2);
4 Internal light (OFF with door closed and ON with
door opened).
oF
58
o.tu
Time relative to auxiliary output oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF
“t” - Keyboard parameters
Parameter Description Range Default
59 t.UF Function mode key
oF No function;
1 Auxiliary output command;
2 Continuous cycle command;
3 Selection of active Set Point (+ light off-eco mode);
4 Switch on/off (Stand-by)
oF
60 t.Fb Function mode key oF
61 t.Lo Keyboard lock function delay oF/0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10) oF
62 t.PP Access Password to parameter functions oF/999 oF
63 t.AS MODBUS address (serial communication) 0 ÷ 255 1