23
4 - Operations
P 1:00
P100:0
P 0:5
P 0:5
P 0:5
P Off
P Off
P Off
P 0
P 1
O.C.
Op. H
hy.
sl. u
sl. d
s.p. l
s.p. H
AIhy
A2hy
t.fil
In.sh
Addr
rt.lo
rt.Hi
pass
tune
PL. rPange
PL. rPange
PH. rPange
PH. rPange
Back to the 1st parameter of the 2nd group
Overshoot control
(PID algorithm only)
0.01…1.00
Control output high limit
(PID algorithm only)
10.0…100.0%
Control output
hysteresis
(ON-OFF control only)
0.1… 10.0% of span
2nd GROUP
Tune run/stop
(PID algorithm only)
Setpoint ramp up
(not available with 2 alarms)
0ff/0.1…999.9 digit/min
Setpoint ramp down
(not available with 2 alarms)
0ff/0.1…999.9 digit/min
Setpoint low limit
(not available with 2 alarms)
low range …
s.p. H
Setpoint high limit
(not available with 2 alarms)
s.p. l…high range
AL1 hysteresis
0.1…10.0% of the span
[1]
AL2 hysteresis
0.1…10.0% of the span
[2]
Password entry
only if
Code
value <5000
(see pages 26…27)
Filter time constant
Off/1...30 s
Input shift
Off/-60 ... 60 digits
Communication address
(if option installed)
0ff/ 1…247
Retransmission
low range
(if option installed)
full scale
Retransmission
high range
(if option installed)
full scale
PARAMETER MENU
Back to the 1st parameter group
Direct access
to the configuration
(pages 26 … 27)
M1UK.ed5 14-05-2009 14:56 Pagina 23

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ascon M1 line and is the answer not in the manual?

ascon M1 line Specifications

General IconGeneral
Brandascon
ModelM1 line
CategoryTemperature Controller
LanguageEnglish

Related product manuals