16
3 - Product coding
3.2 CONFIGURATION CODING
The configuration code consists of
4 digits that identify the operat-
ing characteristic of the controller,
as chosen by the user.
Section 4.5 at pag. 26 reports the
instructions how to set a new con-
figuration code.
The configuration code can be dis-
played on the front panel, follow-
ing the instructions at pag 19 sec-
tion 4.2.2.
I L M N
2002
TC T Cu-CuNi
4
TC K Chromel-Alumel IEC584
5
TC S Pt10%Rh-Pt IEC584
6
Input type and range
I
DC input 0…50 mV, linear
TR Pt100 IEC751
0
7
DC input 10…50 mV, linear
8
Custom input and range
TR Pt100 IEC751
1
9
TC L Fe-Const DIN43710
2
-328…752 °F
TC J Fe-Cu45% Ni IEC584
3
32…2192 °F
32…2912 °F
-99.9…572.9 °F
-328…1112 °F
32…1112 °F
32…1112 °F
-200 …400 °C
0…1200 °C
0…1600 °C
engineering units
-99.9…300.0 °C
engineering units
-200…600 °C
0…600 °C
0…600 °C
2 alarms
indicator
4
Output configuration
5
Control mode
L
Alarm AL1 on OP1/ alarm AL2 on OP2
PID
0
Alarm AL1 on OP2/ alarm AL2 on OP
Control OP1 / alarm AL2 on OP2
1
Control OP2 / alarm AL2 on OP1
ON - OFF
2
Control OP1 / alarm AL2 on OP2
3
Control OP2 / alarm AL2 on OP1
Type of control and safety
M
Reverse (AL1 active low)
Direct (AL1 active high)
0
Safety 0%
1
Safety 0%
Reverse (AL1 active low)
Direct (AL1 active high)
2
Safety 100%
3
Safety 100%
M1UK.ed5 14-05-2009 14:56 Pagina 16