Assa Abloy Lockwood Selector Series - Lock not locking as per switches; Lock remains powered; Double access setup issues

Assa Abloy Lockwood Selector Series
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.assaabloy.co.nz
6
Lock is not locking according to the way
I have set the switches:
The setting switches will not take effect until the lock has fully
powered down. Disconnect all power from the lock and wait at
least 2 minutes and then retry.
If the problem persists, return lock for investigation
Lock is remaining in powered state even
when I send a lock / unlock signal:
The lock may function correctly outside of the door but once the
lock is fitted to the door the lock will not respond to the locking
signal.
If the red and green wires are joined and then the locking
signal is supplied by switching the negative on the black
wire – the lock will not see a change of voltage (as it is
grounded through the door) and will then remain in the
powered state.
A positive (9-29VDC) lock / unlock signal must be supplied on
the lock.
Wiring should be updated to ensure that the locking signal
is switched on the positive side of the supply.
I am trying to set the lock up as double access
(1 side PtL, 1 side PtO) but it is not working as
expected
If the lock is being used in 2 wire mode (red and green wires
joined), then this mode will not operate as required – the lock must
be operated in 3 wire mode for this function to operate correctly.
If the lock is operating in 3 wire mode, is the locking signal on the
green wire PtL?
When entering a power failure state, the PtO side flashes green and
then red – this is normal behavior and due to a minor delay in the
power failure being sensed by the lock – the correct failed state is
achieved.