CAUTION
Wire 12- stand alone unit to appropriate power supply and fire alarm. Earth ground wire connects to green track wire
Refer to data sticker for proper input voltage and current specifications required
Energize power supply. Current draw of .1 AMP per unit
9- Companion units are designed to work with 12- smoke detector units (12-2468, 12-2478, 12-2498) only
Wire companion unit to smoke detector unit as shown on wiring diagram
Do not disconnect any existing wires on smoke detector unit’s terminal strip
Energize power supply
Open door(s) to hold-open point.
Door(s) should hold open
Depress on/off test switch on circuit board.
Door(s) should close and latch
Adjustment of closer spring power may be
necessary to ensure proper latching
Depress on/off test switch to reactivate
hold open latch assembly(s)
Adjust holding tension as required
1
1. DISCONNECT ALL POWER BEFORE BEGINNING
INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE
2. INSTALLER MUST BE A TRAINED EXPERIENCED
SERVICE PERSON
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL
ELECTRICAL CODES, ORDINANCES AND REGULATIONS
4. MAXIMUM WIRE SIZE IS 18AWG
5. SEE IMPORTANT NOTE AT END OF PAGE 7
Wiring 12- Units with and without 9- Companion Unit
Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option
User supplied normally
closed momentary switch
Wiring Optional Remote Push Button
INSTALLER:
LEAVE INSTRUCTIONS
WITH BUILDING OWNER
Wiring Instructions for the SARGENT 2408 Series FIREGUARD
®
Combination Door Closer-Holder and Releasing Device
with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
IMPORTANT NOTE: Fire Alarm Control Panels that cannot ignore a 0.5 second closure during a
power cycle, cannot be used with a 12- Fireguard (smoke detector) product revision “D” and lower.
For more information, see page 7 or contact SARGENT Technical Support at 1-800-810-WIRE(9473).
Copyright
© 2008
SARGENT Manufacturing. All rights reserved.
Reproduction in whole or in part without the express written
permission of SARGENT Manufacturing is prohibited.
A7699C
Question and Answer IconNeed help?

Do you have a question about the Assa Abloy Sargent FIREGUARD 2408 Series and is the answer not in the manual?

Assa Abloy Sargent FIREGUARD 2408 Series Specifications

General IconGeneral
BrandAssa Abloy
ModelSargent FIREGUARD 2408 Series
CategoryDoor Opening System
LanguageEnglish

Related product manuals