For technical support contact Yale
®
at 800.438.1951 or support@yalelocks.com
An ASSA ABLOY Group brand
11
80-9470-0162-000 10/18
Delayed Egress
Exit Device
Installation Instructions
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc.
All rights reserved. Reproduction in whole or in part without the express written
permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
RED(24VDC)
GREEN(24VDC)
REMOTE RESET
REMOTE BYPASS
SECN/C
SECN/O
ALRN/O
BYPASS
GND(-)
24V(+)
24V(+)
GND (-)
CNC
FIRE ALARMTRIGGER SW
Delayed
Egress
Device
TRIGGER SW
RESET
BYPASS
SECN/C
SECN/O
ALRN/O
TRIGGER SW
GND (-)
24V(+)
1
24V(+)
WHITE(+)
WHITE(-)
24V(+)Electrified
RELAY
DPS "H"
ELECTRIFIED TRIM
SAF OR SEC
1
2
3
3
3
4
4
4
4
4
1
2
3
4
ELECTRICTRIMCONTROL
MECHANICALTRIMENTRY WITH SECURITY PACKAGE
MECHANICALTRIMENTRY WITH EXTERNALDOOR POSITIONSWITCH
SINGLE DOOR WITH REMOTE INPUTS ANDMONITORINGOUTPUTS
Foradded security cutthe YELLOWwireonCONNECTOR J1 andattach it
ALRN/C
WHT
ALRN/O
GRN
SECN/O
BLU
SECN/C
ORN
BYPASS
YEL
RESET
BRN
24V(+)
RED
GND (-)
BLK
Connector2
GND (-)
BLK
DPS
BLU
POWER(+)
RED
NC
NC
LOCK
WHT/RED
LOCK
WHT
TRIGGER SW
YEL/WHT
TRIGGER SW
YEL
Connector1
GND(-)
ConnectorJ1
Trim (+)
DelayedEgress
CircuitBoard
Wire Transfer
Hinge
SECURITRON BPS
POWERSUPPLY
24V(+)
GND(-)
NEUTRAL
EARTH
ALARM
ALARM
CARD READER
RI MAND SQUAREBOLT
FAIL SAFE (SAF) OR FAIL SECURE (SEC)
to theDPS switch. The DPS will be in series with the trigger input.
C
NC
NO
CNO
C
NC
CNO
C
120VAC
9 Wiring Options
Figure 10
Operation
Security Package is used to activate alarm when
door has been forced open. It also prevents
device from being armed when door is propped
open.
When activated, “O” trim monitor switch will
bypass unit and allow entry.
Unit must be manually reset for rearming.