installation
electrical connection
The appliance can be connected in the following ways:
Common connections:
2 lives with 2 neutrals connection (2 2N a.c. 230 V /
50 Hz / Cooking circuit):
The voltage between live and neutral is 230 V a.c. There may
be a voltage of 0 V between the phases if they are connected
to the same phase in the meter cupboard but also 400 V if
they are connected to 2 different phases. Your groups must
be fused with at least 16 A (2x). The connecting power cable
must have a minimum core cross section of 2,5 mm
2
.
3 lives with 1 neutral connection (3 1N a.c. 400 V /
50 Hz / Power circuit):
The voltage between the phases and the neutral is 230 V a.c.
There is a voltage of 400 V between the lives. Fit a
connecting bridge between the connection points 4-5. Phase
3 carries no load. Your groups must be fused with at least
16 A (3x). The connecting power cable must have a minimum
core cross section of 2,5 mm
2
.
GB 30
right zones
left zones
right zones
left zones
700001624100 HL HI6071M.qxp 12-10-2005 12:09 Pagina GB 30