EasyManua.ls Logo

Atag iR 15 - Page 41

Atag iR 15
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation & Servicing instructions ATAG iR-Range
41
Measuring point CO
2
Figure 15.1.a
Step 2: CO
2
check on low load
Set the low load
The low load of the boiler can be set by you as follows:
- Pressonthe-buttonuntiltheminimumvalue(0%)hasbeenreached(lowload)
- Use the measuring tool to carry out a CO
2
control measurement. The detected values must lie in the
measuring range shown below.
The CO
2
value at low load must be lower than the CO
2
value at full load. The measuring procedure must
be carried out, until a constant measuring result is achieved. Please contact ATAG, if the values should lie
outside of the applicable tolerances.
End of measuring:
- Press the ESC button (
button).
Thedeviceswitcheso󰀨.
The display shows for 2 seconds code 180 or 181.
This completes the procedure.
The maximum duration of the commissioning function, without interruption, is 8 minutes.
-
+ +
reset
eco
-
°C
-
-
+ +
reset
eco
%
Measuring point CO
2
Figure 15.1.a
a
CO
2
check on low load (Step 2)
Low load Natural gas (G20) Propane (G31)
CO
2
Example readings
Full load recorded Accepted low range Full load recorded Accepted low range
9.6% 9.3%-7.5% 11.0% 10.9%-8.9%
9.5% 9.2%-7.5% 10.9% 10.8%-8.9%
9.4% 9.1%-7.5% 10.8% 10.7%-8.9%
9.3% 9.0%-7.5% 10.7% 10.6%-8.9%
9.2% 8.9%-7.5% 10.6% 10.5%-8.9%
9.1% 8.8%-7.5% 10.5% 10.4%-8.9%
9.0% 8.7%-7.5% 10.4% 10.3%-8.9%
8.9% 8.6%-7.5% 10.3% 10.2%-8.9%
8.8% 8.5%-7.5% 10.2% 10.1%-8.9%
8.7% 8.4%-7.5% 10.1% 10.0%-8.9%
8.6% 8.3%-7.5% 10.0% 9.9%-8.9%
9.9% 9.8%-8.9%
Values are valid with closed cover/air box.

Related product manuals