EasyManua.ls Logo

Atag Q 25S - Checking the O

Atag Q 25S
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation & Servicing Instructions ATAG Q-Series
35
13.2 Checking the O
2
The O
2
percentage is set by the factory. It has to be checked during inspection,
maintenance and faults.
This can be checked by means of the following procedure:
- Remove the black cover of the gas valve.
- Put the boiler into operation and take care that it can deliver its heat;
- Press the MODE-key for 5 seconds.
- The diplay will show COdE followed by an arbitrary number;
- Select by means of the + or the - key the code C123;
- Press the Store-key to conrm the code (code blinks 1 x);
- Press the MODE-key until SERV is shown;
- Press the STEP-key once until 1 is shown;
alternately 1 and OFF will be shown.
- Calibrate the O
2
meter ;
- Place the lance of the O
2
meter into the check point (see g. 13.2.a);
- Press the + key until the maximum value (in kW) is achieved;
The boiler will burn on full load (value on display in kW)
Natural gas Propane
- O
2
percentage at full load = 4,7% (+/-0,2%) 5,1% (+/-0,2%)
- CO/CO
2
ratio less than 0.004%
- Let the O
2
meter do its measuring procedure.
- Adjust, if necessary, the adjustment screw to correct the O
2
value
(see g. 13.2.b).
Finally, the O
2
percentage at low load must be checked:
- Press on the - button until the minimum value has been reached.
The boiler will be burning at low capacity.
- Leave measuring O
2
to the measuring equipment and check if the measured
O
2
percentage on low load is between following values:
Natural gas Propane
- O
2
percentage at low load between 5,0% and 7,0% 5,1% and 7,0%
- CO/CO
2
ratio less than 0.004%
Contact ATAG Heating when the measured values is outside this range.
Ending the O
2
measuring procedure:
- Press the - key until OFF is shown (keep key pressed).
With this the procedure has ended.
- Replace the black cover on the gas valve and x it with the screw.
adjustment screw
figure 13.2.b
Measuring point
figure 13.2.a

Other manuals for Atag Q 25S

Related product manuals