FG_D6_CCLINK_EN_02 / 2020-06-17
Offset
(byte)
Length
(byte)
Offset
(word)
Read table
(MASTER ← ATEQ)
Write table
(MASTER ATEQ)
Real time measurements
16
4
08(h)
Pressure value (32 bits integer)
Example: Pressure value = 207
On network : 98 28 03 00
00032898(H) → 207000(d)/1000 → 207
X080(h)
Low word (LSW)
Y080(h)
RESERVED
X08F(h)
Y08F(h)
X090(h)
High word (MSW)
Y090(h)
RESERVED
X09F(h)
Y09F(h)
20
4
0A(h)
Pressure unit (32 bits integer)
Example: Pressure unit Pa = 6
On network: 70 17 00 00
00001770(H) → 6000(d)/1000 → 6
X0A0(h)
Low word (LSW)
Y0A0(h)
RESERVED
X0AF(h)
Y0AF(h)
X0B0(h)
High word (MSW)
Y0B0(h)
RESERVED
X0BF(h)
Y0BF(h)
24
4
0C(h)
Flow value (32 bits integer)
Example: Flow value = -0.108
On network: 94 FF FF FF
FFFFFF94(H) → -108(d)/1000 → -0.108
X0C0(h)
Low word (LSW)
Y0C0(h)
RESERVED
X0CF(h)
Y0CF(h)
X0D0(h)
High word (MSW)
Y0D0(h)
RESERVED
X0DF(h)
Y0DF(h)
28
4
0E(h)
Flow unit (32 bits integer)
Example: Flow Unit Pa/s = 8
On network: 40 1F 00 00
00001F40(H) → 8000(d)/1000 → 8
X0E0(h)
Low word (LSW)
Y0E0(h)
RESERVED
X0EF(h)
Y0EF(h)
X0F0(h)
High word (MSW)
Y0F0(h)
RESERVED
X0FF(h)
Y0FF(h)
32
40
10(h)
X100(h)
RESERVED
Y100(h)
RESERVED
X13F(h)
Y13F(h)