4.3 Electric cable size and fuses
Cable size
All cables should be mounted on a horizontal ventilated tray.
See table if cables need to be spaced!
Connect cables in the cubicle with the correct cable lugs. There should be a space of 10 mm
between naked cable parts.
The cable size is stated for a maximum ambient temperature of 46 ˚C (115 ˚F).
For IEC compressors, use 90 °C XLPE cables.
IEC 50 Hz compressors
Compressor type Voltage Cable size Remark
GA 110 VSD 380
2x(3x70mm
2
+35mm
2
)
2 cables, spacing required
GA 110 VSD 400
2x(3x70mm
2
+35mm
2
)
2 cables, spacing required
GA 110 VSD 500
2x(3x50mm
2
+25mm
2
)
2 cables, spacing required
GA 132 VSD 380
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 132 VSD 400
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 132 VSD 500
2x(3x95mm
2
+50mm
2
)
2 cables, spacing required
GA 160 VSD 380
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 160 VSD 400
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 160 VSD 500
2x(3x95mm
2
+50mm
2
)
2 cables, spacing required
IEC 60 Hz compressors
Compressor type Voltage Cable size Remark
GA 110 VSD 380
2x(3x70mm
2
+35mm
2
)
2 cables, spacing required
GA 110 VSD 440
2x(3x70mm
2
+35mm
2
)
2 cables, spacing required
GA 132 VSD 380
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 132 VSD 440
2x(3x120mm
2
+50mm
2
)
2 cables, no spacing
required
GA 160 VSD 380
2x(3x120mm
2
+50mm
2
)
2 cables, spacing required
GA 160 VSD 440
2x(3x120mm
2
+50mm
2
)
2 cables, no spacing
required
CSA/UL 60 Hz compressors