Power Focus 6000 LV EN Installation
© Atlas Copco Industrial Technique AB - 9839 1081 01
13
Pin Function
1 Do not use
2 Do not use
3 Do not use
4 Do not use
5 Do not use
6 Do not use
7 Do not use
8 Do not use
9 Connect a jumper between pin 9
and pin 10
10 See pin 9
Resetting emergency stop
Resetting an activated emergency stop is done by the software.
Emergency stop in Power Focus 6000
The Power Focus 6000 LV is equipped with an infrastructure needed to create an emergency stop func-
tion with redundant breaking according to EN ISO 13849-1 category 3 PL d. The emergency stop function
must be used when using remote start functionality.
The emergency stop function can be used with a supply disconnecting device (such as an EM Stop but-
ton). When pressed down, it breaks the supply voltage to the controller.
The emergency stop function can be used with either a single controller or up to 10 controllers in a single
emergency stop chain. In a multiple controller configuration the emergency stop signal is distributed from
the first controller to all interconnected controllers using the I/O bus interface. The last controller in the
chain returns a feedback signal to indicate that all controllers have received the emergency stop signal.
The event Emergency stop is displayed.
For the emergency stop there is a 24V DC output through the EM Stop terminal on the connector board.
Cabling
EM Stop button cables
Single/Multiple controllers Dimension Maximum length
Single 0.7 mm
2
cable 400 meters
Multiple 1.5 mm
2
cable 50 meters
I/O cables
For connecting multiple controllers with I/O-cables distributing the emergency stop signal, use the maxi-
mum length according to the following table:
AWG 22 cable Maximum total length
4 controllers 200 meters
5 controllers 140 meters
6 controllers 100 meters